Share:
PRODUCTS
Locatin : Products > Instrument Transformers > MV & LV CT PT > Outdoor CT/PT
JZW-72.5 Outdoor Voltage Transformer

JZW-72.5 voltage transformer, epoxy resin casting and outdoor installation, is widely used for measuring current, electric energy and protective relaying in the power system with the frequency of 50Hz or 60 Hz and rated voltage of 66kV or 69kV.

The product can be operated on many circumstances such as the areas of altiplano, tropical area, chillness, coastland and dirtiness etc.

DESCRIPTION

Main technical parameter

1. Highest voltage for equipment: 72.5kV

2. Rated primary voltage: 66/√3kV or 69/√3kV etc

3. Limiting output :2000VA

4. Rated power-frequency withstand voltage: 140kV

5. Rated lightning impulse withstand voltage: 325kV or 350kV

6. Rated insulation level: 72.5/140/325kV or  72.5/140/350 kV

7. Technical standard accords with IEC 60044-2:2003 Part2 Instrument transformers-Part2: inductive voltage transformers or IEEE STD C57.13-2008

Rated primary voltage (kV)

Rated secondary voltage (kV)

Accuracy classes combination

Rated output (VA)

Max output

(VA)

Rated insulation level(kV)

66/√3

69/√3

0.1/√3/0.1/3

0.11/√3/0.11/3

0.2/6P(3P)

150/100

2000

72.5/140/325

0.5/6P(3P)

300/100

1/6P(3P)

500/100

0.1/√3/0.I/√3/0.1/3

0.11/√3/0.I1/√3/0.11/3

0.2/0.2/6P(3P)

75/75/100

1000

0.2/0.5/6P(3P)

50/100/100

0.5/0.5/6P(3P)

150/150/100

Remarks: Upon request we are glad to offer transformers according to other standards or with non-standard technical specs.

Outline drawing


Contact Us

1# International Business Department.

international2@chuangy.com

0086-755-8600 0713

Mobile :+86-138 2379 0397


1F and 4F block B,Jiada R&D Bldg, High-tech Park,Nanshan,Shenzhen,China

Post code:518057



Copyright © 2019. Shenzhen Chuangyin   Co., Ltd. All rights reserved. 粤ICP备11018302号