JDZW2-36 Outdoor Voltage Transformer

 

JDZW2-36 voltage transformer, outdoor epoxy resin casting and double pole insulated VT, is widely used for measuring current, electric energy and protective relaying in the isolated neutral system with the frequency 50Hz or 60Hz and insulation voltage 36 kV (Up to 40.5kV).

The iron core adopts advanced cold-rolled silicon steel sheet. High voltage outgoing line of primary winding was fetched out from top of the product; outgoing line of secondary winding was fetched out from transverse side of the product.

DESCRIPTION

Main technical parameter

1. Rated primary voltage:30 kV or 33 kV or 35 kV  etc.

2. Rated secondary voltage:100 V or 110 V

3. Rated power-frequency withstand voltage: 70kV

4. Rated lightning impulse withstand voltage: 170kV

5. Technical standard accords with IEC 60044-2.2003.

6. Other parameters pls see as follow:

Rated Primary Voltage(kV)

Rated Secondary Voltage(kV)

Accuracy classes combination

Rated output

 (VA)

Thermal limiting current

(VA)

Rated insulation level(kV)

35

33

0.1

0.11

0.2

60

1000

36/70/170

(40.5/95/200)

0.5

120

1

200

0.1/0.1

0.11/0.11

0.2/0.2

25/25

500

0.2/0.5

25/50

0.5/0.5

50/50

Remarks: Upon request we are glad to offer transformers according to other standards or with non-standard technical specs.


Outline drawing

Contact Us

1# International Business Department.

international2@chuangy.com

0086-755-8600 0713

Mobile :+86-138 2379 0397


1F and 4F block B,Jiada R&D Bldg, High-tech Park,Nanshan,Shenzhen,China

Post code:518057



Copyright © 2019. Shenzhen Chuangyin   Co., Ltd. All rights reserved. 粤ICP备11018302号