Technical Data

1、Rated insulation level: 12/28/75kV

2、Rated frequency: 50/60Hz

3、Installation site:  Indoor

4、Technical standard: IEC 60044-1

(IEC 61869-1&2)

DESCRIPTION
Specification 

Rated current ratio(A)

Secondary accuracy classes combination

Rated output

 (VA)

FS

ALF

Rated short-time thermal current (kA/S)

Rated dynamic current ( kA)

Measuring

Protective

0.2(S)

0.5

10P

5~200/5

0.2(S)/0.2(S)

0.2(S)/0.5

0.2(S)/10P

0.5/10P

10

15

15

15

5

(10)

10

80I1n

200I1n

300/5

20

50

400/5

30

75

500/5

30

75

600/5

40

80

800/5

40

80

1000/5

63

105