LFS-12 Current Transformer

LFS-12

CURRENT TRANSFORMER

□  12kV Indoor Single-Phase Epoxy Resin Type


Epoxy resin casting insulation and fully enclosed support

construction, encloses primary & secondary windings and

annular core in the epoxy resin casting body. The product has

two secondary windings (one measuring winding and one

protective winding). It is widely used for measuring current,

electric energy and protective relaying in the power system with

the rated frequency 50Hz or 60Hz and highest voltage for

equipment 12kV.


Technical Data

1、Rated insulation level: 12/28/75kV

2、Rated frequency: 50/60Hz

3、Installation site:  Indoor

4、Technical standard: IEC 60044-1

(IEC 61869-1&2)

DESCRIPTION
Specification 

Rated current ratio(A)

Secondary accuracy classes combination

Rated output

 (VA)

FS

ALF

Rated short-time thermal current (kA/S)

Rated dynamic current ( kA)

Measuring

Protective

0.2(S)

0.5

10P

5~200/5

0.2(S)/0.2(S)

0.2(S)/0.5

0.2(S)/10P

0.5/10P

10

15

15

15

5

(10)

10

80I1n

200I1n

300/5

20

50

400/5

30

75

500/5

30

75

600/5

40

80

800/5

40

80

1000/5

63

105


Outline


Contact Us

Calls:

Switchboard:0086-755-86000443

International Sales :0086-755-860007、00861313823790397

international2@chuangy.com

Room 101 / 401, Building B, Jiada R&D Building, Songpingshan Road No.5, Songpingshan Community, Xili Street, Nanshan District, Shenzhen, China


China Southern:0086-756-3639005、008613923479219

cyty@chuangy.com

No.24, Keji 5th Road, Tangjiawan Town, High-tech Zone, Zhuhai, China


China Eastern:0086-792-6893555、008613767272953

sales6@chuangy.com

No.31 Lushandong Road, Shacheng Industrial Park, Jiujiang County, Jiangxi Province, China



Copyright © 2019. Shenzhen Chuangyin   Co., Ltd. All rights reserved. 粤ICP备11018302号