Share:
PRODUCTS
CY-ECTST2 Three-phase Low PowerCurrent Sensor

Apply to

≤24kV cable (insulated) bus

≤0.72kV low voltage non - insulated bus

Application

> Currents sensor is suitable for smart grid low or medium voltage switchgear insulation bus or cable bus measurement.

> Current sensor is mounted on insulated bus bars, shielded cable connectors or similar type insulated conductors.

DESCRIPTION

Technical Data

Model

CY-ECTST2

Max. system voltage (cable bus)

24kV

Insulation level   

0,66/3kV (0,72/3kV)

Rated   ratio

Phase current

600A/1V(4 times max )

Zero sequence current

20A/0.2V

Accuracy

Phase current

0.5S(5P10)measure, metering, production compatible

Zero sequence current

10P10(<1%@1%~120%In)

Short time thermal current     

20xIn

Burden (load resistance)   

≥20kΩ

Frequency   

50/60 Hz

Operating temperature     

-40°C to +70°C

Current sensor type      

Phase current + zero sequence current sensor

Installation method and size      

  core is mounted on the busbar

Inner diameter 3-Φ85mm(3-Φ110mm)

 bottom installed with screw holes

Standard       

GB/T 20840.8 (GB/T 20840.6)

IEC 60044-8 (IEC 61869-6)

Connection type     

Air plug - lead terminal

   Connecting cable     

RVSP shielded wire L = 3 m (length can be customized)