LZZBJ9-12C1、LZZBJ9-12C2 、 LZZBJ9-12C2Q4 Current Transformer

LZZBJ9-12C1、LZZBJ9-12C2 、 LZZBJ9-12C2Q4

CURRENT TRANSFORMER

□  12kV Indoor Single-Phase Epoxy Resin Type

Epoxy resin casting insulation and fully enclosed support construction,

encloses primary & secondary windings and annular core in the epoxy

resin casting body. The product has the feature of light weight,

omnidirectional installation, withstanding nastiness and dampness. It is

widely used for measuring current, electric energy and protective relaying

in the electrical system with the rated frequency 50Hz or 60Hz and highest

voltage for equipment 12kV



Technical Data

1.Rated insulation level: 12/28/75 kV or 12/42/75 kV

2. Rated frequency: 50/60Hz

3. Installation site: Indoor

4. Technical standard: IEC 60044-1

IEC 61869-1&2

DESCRIPTION

LZZBJ9-12C1 Single Ratio

Rated

transformation ratio(A)

Accuracy classes combination

Rated outputVA

COSФ=0.8

 (ALF)

 (FS)

Short-time thermal current Ith(kA/S)

Rated dynamic current Idyn(kA)

Measuring

Protective

0.2(S)

0.5

10P

10-200/5

0.2(S)/0.2(S)

0.2(S)/0.5

0.2(S)/10P

0.5/10P

0.2S/0.5/10P

0.2/0.5/10P

10

15

15

15

10

15

20

5

(10)

150I1n

375I1n

300/5

31.5

80

400/5

31.5

80

500/5

40

100

600/5

50

125

800/5

20

63

125

1000/5

80

160

12001500/5

80

160

15002000/5

100

160

20002500/5

130

160


LZZBJ9-12C1 Double Ratio

Rated

transformation ratio(A)

Accuracy classes combination

Rated outputVA

COSФ=0.8

 (ALF)

 (FS)

Short-time thermal current Ith(kA/S)

Rated dynamic current Idyn(kA)

Measuring

Protective

0.2(S)

0.5

10P

10-20/5

0.2(S)/0.2(S)

0.2(S)/0.5

0.2(S)/10P

0.5/10P

 

10

15

15

15

10

15

20

5

(10)

1.5

3.75

20-40/5

3

7.5

50-100/5

8

20

100-200/5

15

37.5

200-400/5

30

75

400-800/5

20

63

130

500-1000/5

80

160


LZZBJ9-12C2 Single Ratio 

Rated

transformation ratio(A)

Accuracy classes combination

Rated outputVA

COSФ=0.8

 (ALF)

 (FS)

Short-time thermal current Ith(kA/S)

Rated dynamic current Idyn(kA)

Measuring

Protective

0.2(S)

0.5

10P

10-200/5

0.2(S)/0.2(S)

0.2(S)/0.5

0.2(S)/10P

0.5/10P

0.2S/0.5/10P

0.2/0.5/10P

10

15

15

15

20

10

15

20

5

(10)

150I1n

375I1n

300/5

31.5

80

400/5

31.5

80

500/5

40

100

600/5

50

125

800/5

63

125

1000/5

80

160

12001500/5

80

160

15002000/5

80

160

20002500/5

100

160

25003150/5

130

160


LZZBJ9-12C2Q/4 Double Ratio

Rated

transformation ratio(A)

Accuracy classes combination

Rated outputVA

COSФ=0.8

 (ALF)

 (FS)

Short-time thermal current Ith(kA/S)

Rated dynamic current Idyn(kA)

Measuring

Protective

0.2(S)

0.5

10P

10-200/5

0.2S/10P/10P

0.5/10P/10P

0.2S/0.2S/10P/10P

0.2S/0.5/10P/10P

10

15

15

15

20

10

15

20

5

(10)

150I1n

375I1n

300/5

31.5

80

400/5

31.5

80

500/5

40

100

600/5

50

125

800/5

63

125

1000/5

80

160

12001500/5

80

160

15002000/5

100

160

20002500/5

100

160

25003150/5

100

160







Contact Us

1# International Business Department.

international2@chuangy.com

0086-755-8600 0713

Mobile :+86-138 2379 0397


1F and 4F block B,Jiada R&D Bldg, High-tech Park,Nanshan,Shenzhen,China

Post code:518057



Copyright © 2019. Shenzhen Chuangyin   Co., Ltd. All rights reserved. 粤ICP备11018302号