This series are fully enclosed rest casting construction, protective class is utilized by Rogowski Coil, measuring level Fe based nanocrystalline core; primary winding, secondary winding all sealed inside epoxy resin body, this is supportive type, full installation with low burden. Anti-dirtiness, humanity and maintenance free, long creepage distance improving external insulation. Compatible with rated frequency 50Hz, rated voltage 35kV AC indoor circle for measuring current, energy and relay.

DESCRIPTION

Main technical parameter

1, Rated primary voltage: 35kV

2, Rated insulation level: 40.5/95/185kV

3, Rated secondary output: 0.2A(measuring); 200mV(protective)

4, Local standard:

GB/T 20840.8-2007<<Electronic Current Transformer>>

GB 1208-2006<<Electronic instrument transformer>>

5.       Ambient temperature : -40℃-40℃

6, Altitude: 2000m

7, Installation site : outdoor

Specification:

 

Rated Voltage

Current (A)

Rated

Secondary

Combination

Rated Secondary Voltage

ALF

 

FS

Rated short-time thermal current (kA/S)

Rated dynamic current ( kA)

Measuring

Protection

0.2

0.5

5(10)P

20-400

 

 

0.2/0.5

0.2/5P

0.5/5P

0.2/0.5/5P

0.2/5P/5P

0.2A@

0.5VA

0.2A@

0.5VA

200mV@

10kΩ

 

 

20

 

 

40

 

 

 

10

1001 In

2501 In

500

50

112.5

600

63

130

800

63

130

1000

63

130

1200

80

160

1500

80

160

2000

100

160

 