Share:
PRODUCTS
Locatin : Products > > PRODUCTS > METERING UNITS
17.5(24)kV Overhead Pole Mounted Metering Box with Primary Cable and Arrester Seat,JLSZY2-17.5(24) Combined Transformer
This type of metering box is an outdoor dry three-phase primary metering unit. The medium voltage metering transformer is assembled by 3 single-phase combined transformers, each single-phase combined transformer includes 1 set of CT coil, 1 set of VT coil and lightning arrester connection The seat is made of alicyclic epoxy resin (CEP) vacuum casting solid encapsulation. It has excellent insulation performance and hydrophobicity. The surface is resistant to acid and alkali corrosion, pollution, and UV. It is suitable for outdoor overhead line installation and connection to public power systems. The metering box is equipped with a meter box under the installation base, high and low voltage integrated anti-theft design, fast installation, suitable for electrical energy metering, current and voltage measurement in urban and rural power distribution network lines of equipment with a maximum voltage of 24kV and below.
DESCRIPTION

OMD-17.5,OMD-24

1.General parameters:


No.

item

units

specification

OMD-17.5

OMD-24

1.    

Highest voltage for
equipment Um (r.m.s.)

kV

17.5

24

2.    

rated frequency (fR)

Hz

50, 60 or 50/60

3.    

Rated lightning impulse
withstand voltage (peak)

kV

95110

125150

4.    

Rated power-frequency
withstand voltage on primary

kV

38

50

5.    

Rated power-frequency
withstand voltage on secondary

kV

3

6.    

Number of CTs and VTs

pcs

3VT+3CT

7.    

Standard

/

IEC 61869-1:2007 IEC 61869-2:2012

IEC 61869-3:2011IEC 61869-4:2013

2.Function and application.

Overhead pole mounted primary metering unit Comply with the latest applicable industry standards and local and/or national electrical regulations (such as IEC, IEEE (ANSI), CAN, GOST, CEF). It is used for three-phase overhead power grid energy measurement management and distribution network automation management system. The primary side measurement is more accurate, and the power loss of the line can be effectively measured to reduce losses.


3.Main features

3.1.The medium voltage transformer of the metering unit is composed of 3 single-phase combined transformers, which saves installation space. There is a meter box under the installation base. The high and low voltage integrated anti-stealing design can be installed directly and convenientlyon the pole outdoors.


3.2.The metering unit is equipped with a meter box and connected to the transformer connection. The meter and communication module installation space are reserved in the box, and the meter box door switch, proximity sensor, data debugging port, conversion switch, and door lock seal structure are reserved. To prevent electricity theft.


3.3.The meter box body is made of corrosion-resistant alloy aluminum or low-carbon steel with the same performance and hot-dip galvanized, and the sealing design is weatherproof, acid and alkali corrosion resistant, and UV resistant; 


3.4.The medium voltage combined transformer is insulated with epoxy resin solid encapsulation, the surface is dirt-resistant, UV-resistant, has excellent dielectric and mechanical properties, no oil, no gas, and maintenance free, meeting the requirements of safe operation and environmental protection. 


3.5.The CT of the medium voltage combined transformer can be configured double transformation ratios, and it is convenient to set the conversion switch to change the transformation ratio. The VT is equipped with anti-short circuit and overload protection design to avoid burning and explosion caused by VT short circuit and overload. 


3.6 The cable for the overhead line has been connected to the primary end, and the cable of the corresponding area and length can be configured according to user requirements.


4.Technical parameters.


Current transformer specifications


No

Item

characteristic

1.    

Rated primary current

5A up to 1200A

2.    

Rated secondary current

5Aor1A

3.    

Rated Continuous Thermal Current

120%,125%,150%,200%,etc.

4.    

Rated Short time current (Ith) (thermal 1 second)

80xIpr,100xIpr

5.    

Rated Dynamic Current (Idyn)

2.5xIth

6.    

Rated Output(VA)

5,10,12.5,15,20

7.    

Accuracy Class

0.2S,0.2,0.5S,0.5,1 Metering

8.    

Instrument Security Factor (FS)

5,10,20

9.    

Applicable Standard

IEC: 61869-1&2


Voltage transformer specifications


No

Item

characteristic

OMD-17.5

OMD-24

1.    

Rated primary voltageV)

13200/√313800/√3, 15000/√3,7200,8400,etc.

20000/√322000/√3, 14400, etc.

2.    

Rated secondary voltage(V)

100/√3110/√3, 115/√3, 120/√3, 110,115,120

3.    

Rated Voltage Factor

1.2/Continuous

1.5/30s,1.9/30s,1.9/8h

1.5/30s1.9/30s1.9/8h

4.    

Standard connection

Y-Y connection

5.    

Rated Output(VA)

15,20,25,30,50,75

6.    

Accuracy Class

0.2,0.5,1,3 Metering

7.    

Thermal burden(VA)

500

8.    

Applicable Standard

IEC: 61869-1&3

If the parameter requested exceeds the range of the above table, it can be determined after negotiation with our company.




5.Dimensions and wiring schematic diagram.







6.Special instructions.

The company can design and manufacture specially according to the special requirements of customers.




Contact Us

1# International Business Department.

international2@chuangy.com

0086-755-8600 0713

Mobile :+86-138 2379 0397


1F and 4F block B,Jiada R&D Bldg, High-tech Park,Nanshan,Shenzhen,China

Post code:518057



Copyright © 2019. Shenzhen Chuangyin   Co., Ltd. All rights reserved. 粤ICP备11018302号