OMF-17.5,OMF-24
1.General parameters
No. |
item |
units |
specification |
|
OMF-17.5 |
OMF-24 |
|||
1 |
Highest voltage for
|
kV |
17.5 |
24 |
2 |
rated frequency (fR) |
Hz |
50, 60 or 50/60 |
|
3 |
Rated lightning impulse
|
kV |
95,110 |
125,150 |
4 |
Rated power-frequency
|
kV |
38 |
50 |
5 |
Rated power-frequency
|
kV |
3 |
|
6 |
Number of CTs and VTs |
pcs |
3VT+3CT |
|
7 |
Standard |
/ |
IEC 61869-1:2007、 IEC 61869-2:2012 IEC 61869-3:2011、IEC 61869-4:2013 |
Overhead pole mounted primary metering unit Comply with the latest applicable industry standards and local and/or national electrical regulations (such as IEC, IEEE (ANSI), CAN, GOST, CEF). It is used for three-phase overhead power grid energy measurement management and distribution network automation management system. The primary side measurement is more accurate, and the power loss of the line can be effectively measured to reduce losses.
Current transformer specifications
No |
Item |
characteristic |
1. |
Rated primary current |
5A up to 1200A |
2. |
Rated secondary current |
5Aor1A |
3. |
Rated Continuous Thermal Current |
120%,125%,150%,200%,etc. |
4. |
Rated Short time current (Ith) (thermal 1 second) |
80xIpr,100xIpr |
5. |
Rated Dynamic Current (Idyn) |
2.5xIth |
6. |
Rated Output(VA) |
5,10,12.5,15,20 |
7. |
Accuracy Class |
0.2S,0.2,0.5S,0.5,1 Metering |
8. |
Instrument Security Factor (FS) |
5,10,20 |
9. |
Applicable Standard |
IEC: 61869-1&2 |
No |
Item |
characteristic |
|
OMF-17.5 |
OMF-24 |
||
1. |
Rated primary voltage(V) |
13200/√3,13800/√3, 15000/√3,7200,8400,etc. |
20000/√3,22000/√3, 14400, etc. |
2. |
Rated secondary voltage(V) |
100/√3,110/√3, 115/√3, 120/√3, 110,115,120 |
|
3. |
Rated Voltage Factor |
1.2/Continuous 1.5/30s,1.9/30s,1.9/8h 1.5/30s,1.9/30s,1.9/8h |
|
4. |
Standard connection |
Y-Y connection |
|
5. |
Rated Output(VA) |
15,20,25,30,50,75 |
|
6. |
Accuracy Class |
0.2,0.5,1,3 Metering |
|
7. |
Thermal burden(VA) |
500 |
|
8. |
Applicable Standard |
IEC: 61869-1&3 |
If the parameter requested exceeds the range of the above table, it can be determined after negotiation with our company.
6. Special instructions
The company can design and manufacture specially according to the special requirements of customers