Technical Data
1、Rated secondary current: 5A,1A
2、Power frequency withstand voltage: 3kV
3、Rated frequency: 50/60Hz
4、Installation site: Indoor
5、Technical standard: IEC 60044-1
(IEC 61869-1&2)
Specification
Purpose
Measuring current transformer
Protective current transformer
Double winding current transformer
Rated current ratio
Accuracy class and rated burden(VA)
COSΦ=0.8
0.5
1
10P10
0.5
10P10
150/5
1
1
200/5
1
2.5
1.5
1.5
1.5
300/5
2.5
5
2.5
2.5
2.5
400/5
5
7.5
5
2.5
2.5
500/5
5
7.5
5
5
5
600/5
5
7.5
5
5
5