The “RCTA03 lamp Clamp-on Flexible Rogowski coil current transformer “is dsigned for easy installed in tight spaces and without the need for dismantling the primary busbar or cables .It includes a flexible Rogowski coil probe and electronic modules. The signal from the coil probe can be amplified by the electronic codules through the integration processing . The output signal can be directly used in oscilloscope,digital multimeter or data logger recording instrument

Model:
General data:
.Operating temperature&humidity:0 to 50ºC(32-122ºF), ≦80% RH(No condensate)
.Storage temperature&humidity:-10 to60ºC(14-140ºF), ≦80% RH(No condensate)
.Operating environgment:Indoor ,altitude up to 2000 meters
.Standard safety: IEC61010-1:2001,600V CATⅢ
Dimension:
Eletrical Parameter:
The test environment for the accuracy:23±5 ºC), ≦85%RH
|
Model
Data
|
CY-RCTA03-305
|
|
Current Range
|
60A/600A/6000A(10%-100%In)
|
|
Output Sensitivity
|
500m V/A,5m V/A, 0.5m V/A
|
|
Accuracy
|
±1%(10%-100% In)@45-65Hz
|
|
Phase error
|
±1%(10%-100% In)@45-65Hz ±10º@20kHz
|
|
Linearity error
|
±0.2%(10%-100% In)
|
|
Position Sensitivity
|
±0.2%(The distance from the measured cable to junction is above 20mm
|
|
External Influence
|
±1%Max (more than 200mm from the coil)
|
|
Noise
|
8m V rms (60A)
|
|
Temperature Coefficient
|
2m V rms(60A)
|
|
Frequency Range
|
±0.08% Cof the reading data
|
|
Power
|
Min 100KΩ
|
|
Power
|
2*AA/MN1500/LR6 Battery(400hrs)
Eternal Adapter:4.5V DC
|
|
Power LED indicator
|
ON indication When normal power (Red light goes off after 3 seconds ) low battery indication(Red is always on)
|
|
Overload LED indicator
|
Overload above 120% of the range indication(yellow)
|
|
Operating Voltage
|
600V AC RMS or DC
|
|
Security Level
|
IEC 61010-1:2001,600V CAT Ⅲ)
|
|
Cable length
|
3m(Measuring head to the electronics module )
|
|
Output terminals
|
0.5m cable with safety BNC plug
|
|
Weight
|
230g(measuring head),130g(Electronic modules)
|
Usage instruction: