Features:
.Small size
.Low temperature drift, broad band
.Perfect reaction time
.Current Overland ability
Application:
.Static conversion for DC motor traction static conversion
.Speed regulation of AC frequency conversion, servo motor
.Power supply for battery/welding machine UPS.SMPS
Environment Condition:
Environment temperature |
-40 ºC-+80 ºC |
Air pressure |
70kpa-106kpa |
Relative Humidity |
5%-95%(no condensation) |
Storage Temperature |
-40 ºC-+85 ºC |
Electrical Character:
IPN |
Rated primary current rms |
20 |
A |
IPM |
Primary current range |
AC/DC 0-100 |
A |
VS |
Working Voltage(±5%) |
5 |
V |
Vo |
Output voltage |
1.6±(0.907.IP/IPN |
V |
VREF |
Basic Reference Voltage |
1.65 |
V |
IS |
Current consumption |
7mA@IP=0 53mA@IP=100A |
mA |
P |
Max power loss |
0.28 |
W |
RL |
Load resistance |
﹥2 |
KΩ |
Accuracy:
X |
Accuracy |
±0.5@Ipn |
% |
⊱L |
Linearity error |
<0.3 |
% |
Vos |
Zero offset voltage@TA=25ºC |
5(max) |
mV |
Vom |
Magnetic field offset voltage |
2.9(max)5xIpn |
mV |
TCVo |
Vo temperature drift@-40 ºC-80 ºC |
87.5 |
ppm |
TCVREF |
Output temperature drift @Vom=0 Vot=0 |
50 |
ppm |
Tr |
Step response time(90%Ipn) |
<1 |
Us |
BW |
Band width (-3dB) |
DC-100 |
kHz |
Isolation Feature:
Ud |
AC RMS voltage isolation test 50Hz . 1min |
3 |
Kv |
Uw |
Impact pressure 1.2/50us |
5 |
kV |
Mechanical Dimension:
Usage Instruction:
.Primary current direction should be as per the arrow in CT case
.Primary conductor temperature not more than 100 º C
.When primary conductor fully occupy the CT hole ,then performance of di / dt and response time are the best