CY-ECTD5 Single Phase Low Power Current Sensor

Apply to

≤24kV insulated cable busbar

≤0.72kV low voltage noninsulated busbar

Application

> Current sensor apply to current measurement of cable busbar of low voltage / medium voltage C-GIS switchgear in smart grid ;

> current sensor should be mounted on the insulated cable, shielded cable connector, or any other type of insulated conductor.

DESCRIPTION

Technical Data

Model    

CY-ECTD5

Max. system voltage (cable busabar)   

24kV

Insulation level    

 0,66/3kV (0,72/3kV)

Primary current    

600A(4 times max.)

Short time thermal current   

20xIn

Secondary analog output    

1V(max. 4V)

 Accuracy     

0.5S(5P10) measuring, metering , protection compatible

Burden (load resistance)    

≥20kΩ

Frequency     

50/60 Hz

operating temp.    

-40°C to +70°C

current sensor type    

phase current sensor

 Installation method and size    

cable thro-core installation

hole diameter Φ45mm

installation fixed board equipped

Standard   

GB/T 20840.8 (GB/T 20840.6)

IEC 60044-8 (IEC 61869-6)

Connecting type   

aviation plug--lead terminal

connecting cable   

RVSP Shield line L = 3 m (length can be customized)


Dimensions   unit/mm


Contact Us

1# International Business Department.

international2@chuangy.com

0086-755-8600 0713

Mobile :+86-138 2379 0397


1F and 4F block B,Jiada R&D Bldg, High-tech Park,Nanshan,Shenzhen,China