1# International Business Department.
0086-755-8600 0713
Mobile :+86-138 2379 0397
1F and 4F block B,Jiada R&D Bldg, High-tech Park,Nanshan,Shenzhen,China
Post code:518057
LDZB6-12CURRENT TRANSFORMER
□ 12kV Indoor Single-Phase Epoxy Resin Type
Epoxy resin casting insulation and fully enclosed support
construction, encloses primary & secondary windings and annular
core in the epoxy resin casting body. The product has the feature
of light weight, omni-directional installation, withstanding
nastiness and dampness. It is widely used for measuring current,
electric energy and protective relaying in the electrical system with
the rated frequency 50Hz or 60Hz and highest voltage for
equipment 12kV
Technical Data
1、Rated insulation level: 12/28/75kV
2、Rated frequency: 50/60Hz
3、Installation site: Indoor
4、Technical standard: IEC 60044-1
Specification
Type |
Rated primary current(A) |
Accuracy classes combination |
Rated output (VA) |
Short-time thermal current(kA/S) |
Rated dynamic current(kA) |
LDZB6-12 |
400/5 500/5 |
0.2/0.2 0.2/0.5 0.2/10P15 0.5/10P15 |
10/10 10/15 10/20 15/20 |
31.5/2 |
80 |
600/5 800/5 |
0.2/0.2 0.2/0.5 0.2/10P15 0.5/10P15 |
10/10 10/20 10/30 20/30 |
31.5/2 |
80 |
|
1000/5 1200/5 1500/5 |
0.2/0.2 0.2/0.5 0.2/10P15 0.5/10P15 |
15/15 15/30 15/30 30/30 |
45/2 |
112.5 |