1# International Business Department.
0086-755-8600 0713
Mobile :+86-138 2379 0397
1F and 4F block B,Jiada R&D Bldg, High-tech Park,Nanshan,Shenzhen,China
Post code:518057
![]() |
JDZW18-12R voltage transformer, outdoor epoxy resin casting and full-closed construction, is widely used for measuring current, electric energy and protective relaying in the single-phase or three phase power system with the frequency 50Hz or 60Hz and highest voltage for equipment 12kV
Technical Data
1. Installation site Outdoor
2. Rated Frequency) 50/60Hz
3. Burden power factor CosΦ=0.8(lagging)
4. Technical standard accords with IEC 61869-1:2007, IEC 61869-3:2011
Specification
Type |
Rated primary Voltage(kV) |
Rated secondary Voltage(kV) |
Accuracy classes combination |
Rated output(VA) |
Thermal limiting Output(VA) |
Rated Insulation level (kV) |
JDZW18-12R |
10 11 |
0.1 0.11 |
0.2 |
30 |
600 |
12/28/75(IEC) 12/42/75(GB) |
0.5 |
50 |
|||||
1 |
80 |
|||||
0.22 |
3 |
500 |
600 |
|||
0.1/0.1 0.11/0.11 |
0.2/0.2 |
15/15 |
300/300 |
|||
0.2/0.5 |
15/25 |
Note:Upon request we are glad to offer transformers according to other technical specs.
1# International Business Department.
0086-755-8600 0713
Mobile :+86-138 2379 0397
1F and 4F block B,Jiada R&D Bldg, High-tech Park,Nanshan,Shenzhen,China
Post code:518057