1# International Business Department.
0086-755-8600 0713
Mobile :+86-138 2379 0397
1F and 4F block B,Jiada R&D Bldg, High-tech Park,Nanshan,Shenzhen,China
Post code:518057
![]() |
JDZW14-12 voltage transformer, outdoor epoxy resin casting and full-closed construction, is widely used for measuring current, electric energy and protective relaying in the single-phase or three phase power system with the frequency 50Hz or 60Hz and highest voltage for equipment 12kV
Usage Terms
1. Ambient Temperature -25-40℃
2. Installation Site outdoor
Key Technical Data
A. Rated Frequency: 50-60Hz
B. Load power factor cosΦ=0.8 (lagging)
C. Technical standard accords with IEC60044-2:2003
Type |
Rated primary Voltage (kV) |
Rated secondary Voltage (kV) |
Accuracy classes combination |
Rated output (VA) |
Thermal limiting Output (VA) |
Rated Insulation level (kV) |
JDZW14-12 |
11 |
0.1 0.11 |
0.2 |
60 |
1000 |
12/28/75 |
0.5 |
100 |
|||||
1 |
150 |
|||||
0.22 |
6P |
600 |
1000 |
|||
0.1/0.1 0.11/0.11 |
0.2/0.2 |
25/25 |
500 |
|||
0.2/0.5 |
25/50 |
|||||
0.5/0.5 |
40/40 |
|||||
0.1/0.22 0.11/0.22 |
0.2/6P |
25/500 |
800 |
|||
0.5/6P |
50/500 |
|||||
JDZXW14-12 |
11/ |
0.1/
0.11/ |
0.2/6P |
40/150 |
600 |
|
0.5/6P |
80/150 |
|||||
1/6P |
150/150 |
Remarks: Upon request we are glad to offer transformers according to other technical specs.
Outline Drawing
1# International Business Department.
0086-755-8600 0713
Mobile :+86-138 2379 0397
1F and 4F block B,Jiada R&D Bldg, High-tech Park,Nanshan,Shenzhen,China
Post code:518057