600A insulation cap is matched bushing for full insulated, full sealed and dustproof, anti moisture for nonelectrified bushing. Applicable for 200A busbar bushing or bushing during repairment.
The interface complys with IEEE386, 8.3kV and 15.2kV 600A bushing design.
Parameters
Voltage |
15kV |
25kV |
Rated Current |
600A |
600A |
5min AC Voltage Withstand |
39kV |
54kV |
15min DC voltage withstand |
35kV |
48kV |
Partial Discharge |
15kV,≤10pC |
20kV,≤10pC |
Lightning Impulse Voltage |
95kV |
125kV |
Thermal Current |
23kA,2s |
23kA,2s |
Dynamic Current |
84kA,10ms |
84kA,10ms |
Packing
Insulation Cap
Cleaning Paper
Silicone Grease
Auxiliary Tools
Installation instruction
Certificate
Structure
1、Operating Ring 2、Insulated Layer
3、Outer Shield 4、Screw
5、Grounding Hole
Model Option
Product |
Model |
IEEE 15kV,600A Insulation Cap |
CYS-A(S)JM-15/600 |
IEEE 15kV,600A Insulation Cap |
CYS-A(S)JM-25/600 |