12kV Overhead pole mounted primary metering unit,JLSZVW-12 combined medium voltage transformer

This type of metering box is an outdoor dry three-phase primary metering unit. The medium-voltage metering combination transformer is epoxy resin cast and solid-sealed. It consists of two current transformers and two voltage transformers to form three-phase VV wiring, medium voltage The metering combination transformer is vacuum cast with cycloaliphatic epoxy resin (CEP). It has excellent insulation properties and hydrophobicity. The surface is resistant to acid and alkali corrosion, contamination, and UV. It is suitable for outdoor overhead line installation and connection to public power systems. The metering box can be equipped with a metering meter box. All the secondary leads of the transformer can be connected and collected in the meter box. It is also equipped with a test terminal block and a meter installation space. The meter can be configured according to the requirements or the user can configure the meter. Just plug in, and it is suitable for electrical energy metering, current and voltage measurement in urban and rural power distribution network lines with a maximum voltage of 12kV and below.

DESCRIPTION

 JLSZVW-12(OMV-12) 


1.1 Basic parameters:

No.

Item

Units

Specification

1.    

Highest voltage for
equipment Um (r.m.s.)

kV

12

2.    

rated frequency (fR)

Hz

50, 60 or 50/60

3.    

Rated lightning impulse
withstand voltage (peak)

kV

75 kV95 kV

4.    

Rated power-frequency
withstand voltage on primary

kV

28

5.    

Rated power-frequency
withstand voltage on secondary

kV

3

6.    

Number of CTs and VTs

pcs

2VT+2CT

7.    

Standard

/

IEC 61869-1:2007 IEC 61869-2:2012 IEC 61869-3:2011IEC 61869-4:2013

2. Product function and use:
Overhead pole mounted primary metering unit Comply with the latest applicable industry standards and local and/or national electrical regulations. It is used for three-phase overhead power grid energy measurement management and distribution network automation management system. The primary side measurement is more accurate, and the power loss of the line can be effectively measured to reduce losses.
3. Main features of the product:
1. The integrated solid package of the medium voltage combined transformer of the metering unit has a compact and beautiful design, eliminating the need for multiple single transformer combined installation and ring connection, and can be installed directly on the pole outdoors, which is convenient and quick;
2. The metering unit can be equipped with a meter box as required and connected to the transformer connection. The meter is installed in the box, and the meter box door switch sensor alarm signal is reserved. The door lock seal structure is designed to prevent electricity theft;
3. The meter box body is made of corrosion-resistant stainless steel or low-carbon steel of the same performance, and the sealing design is weather-proof, and the surface is coated with an anti-corrosion paint powder layer, which is resistant to acid and alkali corrosion and UV;
4. The medium voltage combination transformer is insulated with epoxy resin solid encapsulation, and the surface is dirt-resistant, UV resistant, and has excellent dielectric and mechanical properties. Compared with the dispersed single-phase combination transformer, its size is more compact, oil-free, gas-free Maintenance to meet the requirements of safe operation and environmental protection;
5. The CT of the medium voltage combined transformer can be configured with double transformation ratios, and it is convenient to set the changeover switch. The VT is equipped with anti-short circuit and overload protection design to avoid burning and explosion caused by VT short circuit and overload.

6. The primary connection adopts the contact bar and the terminal clamp connection. The terminal block of the corresponding area can be configured according to the user's requirements, the lightning arrester mounting bracket is reserved, and the lightning arrester can be configured at the primary end as required.


4. Product technical parameters:
Current transformer specifications

No

Item

Specification

1.    

Rated primary current

5A up to 1000A

2.    

Rated secondary current

5A1A

3.    

Rated Continuous Thermal Current

120%,125%,150%,etc.

4.    

Rated Short time current (Ith) (thermal 1 second)

80xIpr,100xIpr

5.    

Rated Dynamic Current (Idyn)

2.5xIth

6.    

Rated Output(VA)

5,10,12.5,15,20

7.    

Accuracy Class

0.2S,0.2,0.5S,0.5,1 Metering

8.    

Instrument Security Factor (FS)

5,10

9.    

Applicable Standard

IEC: 61869-1&2

Voltage transformer specifications

No

Item

Specification

1.    

Rated primary voltage(V)

1000011000

2.    

Rated secondary voltage(V)

100110115120

3.    

Rated Voltage Factor

1.2/Continuous

1.5/30s

4.    

Standard connection

V-V connection

5.    

Rated Output(VA)

15,20,25,30,50,75

6.    

Accuracy Class

0.2,0.5,1,3 Metering

7.    

Thermal burden(VA)

300

8.    

Applicable Standard

IEC: 61869-1&3



If the parameters required by the user exceed the range of the above table, it can be determined after consultation with our company.


5. Product dimensions and wiring schematic diagram:



Dimentions



6、special instructions
The company can design and manufacture specially according to the special requirements of customers.