This type of metering box is an outdoor dry three-phase primary metering unit. The medium-voltage metering combination transformer is epoxy resin cast and solid-sealed. It consists of two current transformers and two voltage transformers to form three-phase VV wiring, medium voltage The metering combination transformer is vacuum cast with cycloaliphatic epoxy resin (CEP). It has excellent insulation properties and hydrophobicity. The surface is resistant to acid and alkali corrosion, contamination, and UV. It is suitable for outdoor overhead line installation and connection to public power systems. The metering box can be equipped with a metering meter box. All the secondary leads of the transformer can be connected and collected in the meter box. It is also equipped with a test terminal block and a meter installation space. The meter can be configured according to the requirements or the user can configure the meter. Just plug in, and it is suitable for electrical energy metering, current and voltage measurement in urban and rural power distribution network lines with a maximum voltage of 12kV and below.
JLSZVW-12(OMV-12)
1.1 Basic parameters:
No. |
Item |
Units |
Specification |
1. |
Highest voltage for |
kV |
12 |
2. |
rated frequency (fR) |
Hz |
50, 60 or 50/60 |
3. |
Rated lightning impulse |
kV |
75 kV,95 kV |
4. |
Rated power-frequency |
kV |
28 |
5. |
Rated power-frequency |
kV |
3 |
6. |
Number of CTs and VTs |
pcs |
2VT+2CT |
7. |
Standard |
/ |
IEC 61869-1:2007、 IEC 61869-2:2012 IEC 61869-3:2011、IEC 61869-4:2013 |
6. The primary connection adopts the contact bar and the terminal clamp connection. The terminal block of the corresponding area can be configured according to the user's requirements, the lightning arrester mounting bracket is reserved, and the lightning arrester can be configured at the primary end as required.
No |
Item |
Specification |
1. |
Rated primary current |
5A up to 1000A |
2. |
Rated secondary current |
5A或1A |
3. |
Rated Continuous Thermal Current |
120%,125%,150%,etc. |
4. |
Rated Short time current (Ith) (thermal 1 second) |
80xIpr,100xIpr |
5. |
Rated Dynamic Current (Idyn) |
2.5xIth |
6. |
Rated Output(VA) |
5,10,12.5,15,20 |
7. |
Accuracy Class |
0.2S,0.2,0.5S,0.5,1 Metering |
8. |
Instrument Security Factor (FS) |
5,10 |
9. |
Applicable Standard |
IEC: 61869-1&2 |
Voltage transformer specifications
No |
Item |
Specification |
|
1. |
Rated primary voltage(V) |
10000,11000 |
|
2. |
Rated secondary voltage(V) |
100,110,115,120 |
|
3. |
Rated Voltage Factor |
1.2/Continuous 1.5/30s |
|
4. |
Standard connection |
V-V connection |
|
5. |
Rated Output(VA) |
15,20,25,30,50,75 |
|
6. |
Accuracy Class |
0.2,0.5,1,3 Metering |
|
7. |
Thermal burden(VA) |
300 |
|
8. |
Applicable Standard |
IEC: 61869-1&3 |
If the parameters required by the user exceed the range of the above table, it can be determined after consultation with our company.
5. Product dimensions and wiring schematic diagram:
Dimentions
6、special instructions
The company can design and manufacture specially according to the special requirements of customers.
1# International Business Department.
0086-755-8600 0713
Mobile :+86-138 2379 0397
1F and 4F block B,Jiada R&D Bldg, High-tech Park,Nanshan,Shenzhen,China
Post code:518057