Features:
.Flexible and light weights
.Easy& quick installation in tight spaces
.No danger from open-circuited secondary
.No core saturation or damage if overloaded
.Excellent linearity
.Multi-size are available
Applications:
.Power quality monitoring .Power meters .Smart logger .Energy sub-meters .Distributed measurement systems
The”RCT02 Clamp-on Flexible Rogowski coil current transformer” are designed for easy installed in tight spaces and without the need for dismantling the primary busbar or cables.
Model Code:
General data:
.Ambient operating temp.:-20……+70
.Ambient storage temp.:-25……+75
.Standards safety: IEC 61010-1:2001,600V CATⅢ
Dimension: Unit:mm
Dimensions(mm) |
CY-RCT02-120 CY-RCTA02-120 |
CY-RCT02-150 CY-RCTA02-190 |
CY-RCT02-305 CY-RCTA02-305 |
WindowA |
120 |
190 |
305 |
Coil OD B |
145 |
205 |
335 |
Coil Length C |
400 |
600 |
1000 |
Output connection |
UL2586-ESB2*24AWG L =150cm(as required) Coax terminated with safety male BNC connector L =300cm(as required) UL 2586-ESB2.24AWG L=150cm(as required)with integrator |
Electrical Parameter:
Model No
Date |
CY-RCT02-120 |
CY-RCT02-120 |
CY-RCT02-120 |
CY-RCT02-120 |
CY-RCT02-120 |
CY-RCT02-120 |
|||||||
Current Range |
10A-30K A |
10A-6000A |
|||||||||||
Frequency |
25H z-20k Hz |
45Hz-600Hz |
|||||||||||
Output Voltage |
Rated curent |
1000A |
2000A |
3000A |
1000A,1500A 2000A,3000A |
2000A,3000A 5000A,6000A |
3000A,4000A 5000A,6000A |
||||||
50Hz |
100Mv AC |
200Mv AC |
300Mv AC |
333mV |
|||||||||
1mV/A@1000……3000A(0.5mV/A@4000……6000A) |
|||||||||||||
Max output |
/ |
3.0V AC max |
|||||||||||
Accuracy |
<1%@25ºC(45-65Hz) |
<1%@25ºC(45-65Hz) |
|||||||||||
Phase error |
<60@25ºC(45-65Hz) |
<60@25ºC(45-65Hz) |
|||||||||||
Output sensitivity |
±0.5@25ºC (With calibration) |
1% |
|||||||||||
±2%Max(No calibration) |
|||||||||||||
Linearity error |
±0.2% (10%-100%II n) |
±0.2% |
|||||||||||
Position Sensitivity |
±2% |
±2% |
|||||||||||
External Influence |
±2%Max |
±1.5%Max |
|||||||||||
Power Supply |
/ |
10-30VDC,30mA Max. |
Linerity&Phase angel error graph Position Sensitivity: