Apply to
≤24kV insulated cable busbar
≤0.72kV low voltage noninsulated busbar
> Current sensor apply to current measurement of cable busbar of low voltage / medium voltage C-GIS switchgear in smart grid ;
> current sensor should be mounted on the insulated cable, shielded cable connector, or any other type of insulated conductor.
Model |
CY-ECTD5 |
Max. system voltage (cable busabar) |
24kV |
Insulation level |
0,66/3kV (0,72/3kV) |
Primary current |
600A(4 times max.) |
Short time thermal current |
20xIn |
Secondary analog output |
1V(max. 4V) |
Accuracy |
0.5S(5P10) measuring, metering , protection compatible |
Burden (load resistance) |
≥20kΩ |
Frequency |
50/60 Hz |
operating temp. |
-40°C to +70°C |
current sensor type |
phase current sensor |
Installation method and size |
cable thro-core installation |
hole diameter Φ45mm |
|
installation fixed board equipped |
|
Standard |
GB/T 20840.8 (GB/T 20840.6) IEC 60044-8 (IEC 61869-6) |
Connecting type |
aviation plug--lead terminal |
connecting cable |
RVSP Shield line L = 3 m (length can be customized) |