Technical Data
1. Rated insulation level: 24/50/125 kV
2. Rated frequency: 50/60Hz
3. Installation site: Outdoor
4. Technical standard: IEC 60044-2, IEC 61869-1&3
Specification
Rated transformation ratio(A) |
Accuracy classes combination |
(VA) Rated output |
||
Measuring |
Protective |
|||
0.2(S) |
0.5 |
10P10 |
||
400/5 |
0.2(S)/0.2(S) 0.2(S)/0.5 0.5/0.5 0.2(S)/10P10 0.5/10P10 |
15 |
15 |
15 |
500/5 |
15 |
15 |
15 |
|
600/5 |
15 |
15 |
15 |
|
800/5 |
20 |
20 |
20 |
|
1000/5 |
20 |
20 |
20 |
|
1500/5 |
20 |
20 |
20 |
|
2000/5 |
30 |
30 |
30 |
|
3000/5 |
30 |
30 |
30 |
|
4000/5 |
40 |
40 |
40 |
|
5000/5 |
40 |
40 |
40 |
|
6000/5 |
60 |
60 |
60 |
|
8000/5 |
60 |
60 |
60 |
|
10000/5 |
60 |
60 |
60 |
Note:Upon request we are glad to offer transformers according to other technical specs.